Emergency lighting must provide adequate illumination when normal power fails, helping occupants find exits and responders work safely. A batterys amp-hour (Ah) rating alone does not establish how long a system will operate. Runtime also depends on the emergency load, battery discharge characteristics, system losses, temperature, battery condition, and applicable requirements.
This guide outlines a practical process for estimating, selecting, and verifying battery runtime. It is general guidancenot a substitute for applicable codes, manufacturer instructions, or approval by the authority having jurisdiction (AHJ).
First, identify the requirements that apply to the building and installation. These may vary with the buildings use and location, the system type, local amendments, and the AHJ. Review the applicable building and fire codes, referenced standards, project specifications, and approval conditions. Do not assume that one operating duration applies to every installation.
Also establish what the system must accomplish during that period. Runtime alone does not prove that an installation is adequate: emergency luminaires must provide the required illumination and distribution for the required duration.
Record:
List every device powered by the battery during an outage. Depending on the system, this may include luminaires, drivers, inverters, controls, sensors, indicators, and other connected equipment.
Use the emergency-mode input power wherever possible. A luminaires advertised lamp wattage may not equal the power drawn from the battery, especially when a driver or inverter is involved. For systems with multiple operating modes, use the load and operating sequence required by the project and applicable rules.
For a simple, constant-power load, an initial estimate is:
[
\text{Ideal runtime (hours)}
=
\frac{\text{Nominal battery energy (Wh)}}{\text{Emergency load (W)}}
]
Nominal battery energy can be estimated as:
[
\text{Nominal energy (Wh)}
\approx
\text{Capacity (Ah)} \times \text{Nominal voltage (V)}
]
For example, a 12 V, 24 Ah battery has a nominal energy of approximately 288 Wh. Dividing 288 Wh by a 10 W load gives an idealized estimate of 28.8 hours.
This is not a reliable runtime prediction. It assumes all rated energy is usable and does not account for discharge conditions, cutoff voltage, system losses, temperature, battery aging, or other limits. Use it only as an initial comparisonnot as a basis for final design approval.
Actual runtime is generally lower than an ideal energy calculation suggests. Consider the following factors:
Where available, use manufacturer runtime tables, discharge curves, or constant-power data for the exact battery and operating conditions. If the load varies over time, use the manufacturers data or an accepted calculation method that reflects the load profile.
Battery chemistry affects capacity, charging, service life, temperature performance, maintenance, and safety. Common options include lead-acid, nickel-cadmium, and lithium-ion batteries, but performance varies by product and configuration.
When comparing batteries, check:
Do not choose a chemistry based on energy density or cycle-life claims alone. Confirm that the complete battery and lighting system suit the site, charging arrangement, and relevant safety requirements.
Temperature can affect both available capacity and long-term battery life. Check the manufacturers specified charging, discharging, and storage temperature ranges against actual installation conditions. Enclosures, ceiling spaces, plant rooms, and outdoor locations may experience temperatures that differ substantially from those in occupied spaces.
Also account for performance over the batterys service life. Age, charging history, maintenance, and previous discharge events can reduce available capacity. Design and maintenance plans should reflect the expected end-of-life condition, not only the performance of a new, fully charged battery.
Request documentation for the specific model and configuration under consideration. A useful runtime claim should identify:
A batterys capacity rating alone does not establish that an emergency-lighting system meets its required duration. Where required, verify performance using the prescribed test or another accepted, documented method with the actual product configuration.
A compliant design depends on ongoing maintenance. Follow the applicable code, standard, manufacturer instructions, and site procedures for inspection and testing. Keep records of test dates, results, faults, repairs, and battery replacements.
The maintenance plan should specify:
Testing intervals and methods vary by jurisdiction and system type. Confirm the requirements for the installation rather than relying on a generic schedule.
Before approving a battery or emergency-lighting system, confirm that you have:
Reliable emergency-lighting runtime is determined by the complete system, not by battery capacity in isolation. Start with the applicable requirements, establish the full emergency load, and use product-specific performance data that reflects real operating conditions. Then verify the system as required and maintain it throughout its service life. This approach helps ensure that emergency lighting provides both the required duration and useful illumination when normal power is lost.